每星期空載試機一次,運轉時間10-15分鐘,以便及時發現問題,並確保蓄電池有足夠容量供發電機啟動。
1.保養前應切斷發電機自動空氣開關,主開關置於停止位置,折開蓄電池正負級電源線,確認發電機不能啟動。
2.檢查蓄電池電解液水位,不足時應依其濃度加入硫酸溶液或蒸餾水。
3.計算發電機距上次養的累積運轉時間,空氣濾淨器每50小時應清潔一次,機油濾淨器、柴油濾淨器、水過濾器每250小時更換一次濾芯。
4.檢查機組是否有漏水、漏油現象,清潔發電機機身。
5.接妥蓄電池電源線及接頭,測試故障顯示燈應全亮。
6.檢查接地線是否良好。
7.檢查機房抽風機運轉狀況,柴油油量是否足夠運轉八小時。
8.檢查冷郤水水位、機油油位是否正常。
9.手動試機運轉正常後,打開發電機自動空氣開關,主開關切至自動啟動位置,進行模擬停電測試,觀察發電機自動啟動狀況。
10.發電機帶負荷運轉一小時,觀察各儀表指示和機組運轉是否正常。
11.填寫運轉記錄及保養記錄。
---------------------------------------------------------------------------------------------------------
No-load test machine once a week, running time 10-15 minutes, in order to detect problems and ensure that the battery has enough capacity for the generator to start.
1. Maintenance of the generator should be turned off before the automatic air switch, main switch in the stop position, fold open the battery positive and negative grade power cord, make sure the generator does not start.
2 Check the battery electrolyte level, lack of concentration should be according to their solution or distilled water by adding sulfuric acid.
3 calculated from the last generator to support the cumulative operation time, air purifiers should be cleaned once every 50 hours, oil purifiers, diesel purifiers, water filters every 250 hours to replace a filter.
4 Check unit for leaks, oil leaks, clean the generator body.
5 power cord connected properly and the battery connector, test failure indicator light should be full.
6 Check the ground wire is good.
7 Check the engine room exhaust fan operating conditions, the adequacy of diesel fuel running eight hours.
8 Check cooling water level, oil level is normal.
9. Manual test machine is operating normally, open the generator automatically switches the air, the main concern to start automatically open position, to simulate the power test, the generator automatically starts observing the situation.
10 generators with a load operation for one hour, observe the meter indication and the unit is functioning properly.
11 complete running records and maintenance records.